12.3 System Trouble Diagnosis through System Error
Codes
When the ERR indicator of DVP15MC11T blinks or is always ON, users can get to know the cause of an
error and shoot the trouble through selecting menu Device > Diagnosis Information… in the CANopen
Builder software of version 6.0 or above.
System error code
Explanation Correction
Hexadecimal
Decimal
0x1000 4096 Internal RAM detection failed
Contact local technicians if the error still exists
after repower on.
0x1001 4097
Internal Flash detection failed
0x1002 4098
The extension port detection
failed
0x1003 4099
Internal voltage is abnormal (LV)
Adjust input voltage to 24V at the power port.
0x1004 4100 Flash initializing failed
Contact local technicians if the error still exists
after repower on.
0x1005 4101 Flash ID detection failed.
0x1007 4103
The access to flash failed in the
Ethernet area.
Contact local technicians if the problem still
exists after re-downloading the program and
restoring the setting to the factory setting.
0x1008 4104
The access to flash failed in the
extension area.
0x1009 4105
The access to flash failed in the
program area.
0x100A 4106
The access to flash failed in the
CAN motion area.
0x100B 4107
The access to flash failed in the
Task area.
0x100C 4108
The access to flash failed in the
CANopen communication.
0x100D 4109
The access to flash failed in the
hardware configuration.
0x100E 4110
The access to flash faild in the
CAM area.
0x100F 4111
The access to flash (the flash
management table) failed.
0x1010 4112
The access to flash (sheet
1 in the
flash management table) failed.
0x1011 4113
The access to flash (sheet
2 in the
flash management table) fails.
0x1012 4114 The reading of flash failed.
0x1013 4115 The writing in flash failed.
0x1014 4116
The erasing of the content in flash
failed.
0x1015 4117
CNC file ID is out of the allowed
range
Check if the CNC file ID is larger than 64.
Update the software and redownload the
program if the error still exists after
redownloading the program.
0x1016 4118
The size of CNC
file exceeds the
range
CNC file is too large in size. Diminish the size
and redownload the program.
0x1017 4119
The position of i
ncremental
encoder 1 changes dramatically in
Check if the input of the encoder is too fast or
12-12

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta Electronics DVP15MC11T and is the answer not in the manual?

Delta Electronics DVP15MC11T Specifications

General IconGeneral
BrandDelta Electronics
ModelDVP15MC11T
CategoryController
LanguageEnglish

Related product manuals