EasyManuals Logo

Delta Electronics DVP15MC11T User Manual

Delta Electronics DVP15MC11T
601 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #529 background imageLoading...
Page #529 background image
DVP15MC11T Operation Manual
12
1
System error code
Explanation Correction
Hexadecimal
Decimal
0x300B 12299
It is detected that data types are
illegal in the program.
Update the software
if the error still exists after
re-compiling and re-downloading the program
and repowering the product.
0x300C 12300
The length of data type String is
too large.
The number of characters in String data type is
too large. Update the software if the error still
exists after modifying the program,
re-compiling and re-downloading the program.
0x300D 12301
Illegal addressing method for
variables
Update the software
if the error still exists after
re-compiling and re-downloading the program
and repowering the product.
0x3020 12320
The checksum of the downloaded
CAN Motion configuration is
illegal.
Update the software
if the error still exists after
re-compiling and re-downloading the program
and repowering the product.
0x3021 12321
The checksum of the downloaded
extension configuration is illegal.
0x3022 12322
The checksum of the downloaded
program is illegal.
0x3023 12323
The checksum of the downloaded
task data is illegal.
0x3024 12324
The checksum of the downloaded
CANopen data is illegal.
0x3025 12325
The checksum of the downloaded
hardware configuration is illegal.
0x3026 12326 Watchdog timeout
Check if the program is correct or there is a
loop of which the program execution can not
get out when the program execution timeout
occurs.
0x3027 12327
Calling the axis state machine
failed.
Contact local technicians
if the error still exists
after redownloading the program and restoring
to the factory setting.
0x3028 12328 CNC list analysis error
Check if the CNC file is correct and
redownload the program.
0x3029 12329 CNC file analysis error
Check if the CNC file is correct and
redownload the program.
0x3050 12368
The actual time for executing the
priority 0 task exceeds the set
watchdog timeout time.
Contact local distributors
0x3051 12369
The
actual time for executing the
priority 1 task exceeds the set
watchdog timeout time.
1. Reset the watchdog time to a larger value
for the task.
2. Check whether there is any infinite loop
in the program which the task calls.
3. Redownload it after modifying the
program.
0x3052 12370
The actual time for executing the
priority2 task exceeds the set
watchdog timeout time.
1. Reset the watchdog time to a larger value
for the task.
2. Check whether there is any infinite loop
in the program which the task calls.
3. Redownload it after modifying the
program.
0x3053 12371
The actual time for executing the
priority 3 task exceeds the set
1. Reset the watchdog time to a larger
12-14

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta Electronics DVP15MC11T and is the answer not in the manual?

Delta Electronics DVP15MC11T Specifications

General IconGeneral
BrandDelta Electronics
ModelDVP15MC11T
CategoryController
LanguageEnglish

Related product manuals