6-26
Ultron HPH Series
11
Press the ON/ OFF button ( ) once and the following screen will pop up to ask you
if you want to power on the UPS’s inverter. Please select ‘YES’.
Standby
MEASUREMENT
Power Flow
UPS-1.1 SETUP MAINTENANCE EVENT LOG
POWER ON ?
No
Yes
09:30
May 10,2018
LOG IN
Administrator
(Figure 6-31: Power on Reminder Screen)
12
After selection of ‘YES’ to start up the UPS’s inverter, each power module will start
up and perform self-inspection. After the self-inspection is completed, the UPS will
automatically transfer to run in frequency conversion mode and the output frequency
will be the same as setup value. Now, the tri-color LED indicator illuminates green and
the following screen appears. For the tri-color LED indicator location, please refer to
Figure 2-12.
Frequency
Conversion
MEASUREMENT MAINTENANCE EVENT LOGLOG IN
AdministratorPower Flow
UPS-1.1 SETUP
POWER FLOW
Maintenance
Bypass
Bypass
Mains
90 %
5 mins
Load
30 %
Power Flow
Summary
System Status
09:30
May 10,2018
(Figure 6-32: Frequency Conversion Mode Screen)