7-26
Ultron HPH Series
7.10.4 Battery & Charging Setting
Path:
SETUP
ĺ%DWWHU\&KDUJLQJ6HWWLQJ
In the BATTERY & CHARGING SETTING screen (shown in the figure below), the user
can set up the following items. These settings must be carried out by qualified service
personnel. Please contact Delta customer service for assistance.
Bypass
240
V
220
V
210
V
272
V
280
V
45
A
UPS-1.1
SETUP MAINTENANCE EVENT LOGLOG IN
Administrator
MEASUREMENT
Battery & Charging Setting
BATTERY & CHARGING SETTING
1
PAGE
3
PAGE
2
PAGE
4
PAGE
Battery Type
PbAc
Battery Rating Voltage
Submit
Battery Low Warning Battery Cut Off Voltage
Float Charge Voltage Equalized Charge Voltage Charge Current (Max)
450
A
Capacity
Battery Strings
1
09:30
May 10,2018
Bypass
480
min
UPS-1.1
SETUP MAINTENANCE EVENT LOGLOG IN
Administrator
MEASUREMENT
Battery & Charging Setting
BATTERY & CHARGING SETTING
1
PAGE
3
PAGE
2
PAGE
4
PAGE
Auto Equalized Charge
Disable
Auto Equalized Charge Interval Equalized Charge Time
1 Month
09:30
May 10,2018