3-27
3
Operation Modes
3.2.11
Manual Bypass Mode_ Dual Input_ Parallel Units
,QSDUDOOHOPRGHLIRQHRIWKHSDUDOOHO836VQHHGVPDLQWHQDQFHSOHDVH¿UVWFRQ¿UPWKDW
WKHE\SDVV$&VRXUFHDQGHDFKSDUDOOHO836¶V676PRGXOHDUHQRUPDO$IWHUFRQ¿UPDWLRQ
please follow the procedures below to manually switch each of the parallel UPSs to manual
bypass mode.
1
Press each LCD’s ON/ OFF button ( ) once and the POWER OFF? screen will
SRSXSWRDVN\RXLI\RXZDQWWRSRZHURႇWKH836¶VLQYHUWHU3OHDVHVHOHFWµYES’.
2
Turn on each UPS’s Manual Bypass Switch (Q3).
3
7XUQRႇHDFK836¶V%\SDVV6ZLWFK4
4
7XUQRႇHDFK836¶V,QSXW6ZLWFK4DQG2XWSXW6ZLWFK4
5
7XUQRႇHDFKH[WHUQDOEDWWHU\FDELQHW¶VEUHDNHU4
In manual bypass mode, all power inside the parallel UPSs is completely cut off and
maintenance personnel can perform maintenance safely. The connected critical loads will
be supplied by manual bypass. During manual bypass mode, all parallel UPSs’ tri-color
/('VDQG/&'VDUHRႇ3OHDVHVHHFigure 3-26 for the path of electrical power through the
parallel UPSs in manual bypass mode.
WARNING:
1. In manual bypass mode, make sure that all of the switches and breakers (except
each UPS’s Manual Bypass Switch (Q3)) are in the OFF position before
working on any of the parallel UPSs’ internal circuits. This avoids electric
shock.
 $IWHUWKHSRZHULQVLGHDOOSDUDOOHO836VLVFRPSOHWHO\FXWRႇWKHUHLVQRKLJK
voltage inside the parallel UPSs except each UPS’s wiring terminals and
Manual Bypass Switch (Q3). Do not touch any UPS’s wiring terminals and
Manual Bypass Switch (Q3) during UPS maintenance process to avoid electric
shock.
3. During manual bypass mode, the parallel UPSs’ input power is completely cut
RႇDQGWKHFRQQHFWHGFULWLFDOORDGVDUHQRWSURWHFWHG
NOTE:
)RUSDUDOOHO836VLI\RXZDQWWRWXUQRႇRQHRIWKHSDUDOOHO836VIRUPDLQWHQDQFH
please make sure the connected critical loads will not exceed the remaining
parallel units’ total capacity.