When you see the following alarm messages appear on the LCD, please follow the solutions shown
below. If you see other alarm messages that are not listed in the table below, please contact Delta
service personnel for assistance. Do not perform troubleshooting if you are not trained for it.
No.
Alarm
Message
Possible Cause Solution
1
Mains Input
Volt/ Freq Out
Range
1. The input switch is
turned off.
2. The main AC source’s
voltage or frequency is
abnormal.
1. Please check if the input switch is turned off
or not. If yes, please turn it on.
2. Please check if the main AC source’s
voltage or frequency is abnormal or not. If
yes, please wait for the main AC source to
be restored.
3. If the alarm message still exists after the
solutions mentioned above have been
executed, please contact service personnel.
2
Mains Input
Volt Phase
Seq Abnormal
The wiring is incorrect.
Please check the wiring and phase sequence
of the main AC source, and contact service
personnel for assistance.
3
Mains Input
%UHDNHU2ႇ
The input switch is
WXUQHGRႇ
1. Please check if the input switch is turned off
or not. If yes, please turn it on.
2. If the alarm message still exists after
the solution mentioned above has been
executed, please contact service personnel.
4
Bypass Input
Volt Out
Range
1. The bypass switch is
turned off.
2. The bypass AC source’s
voltage is abnormal.
1. Please check if the bypass switch is turned
off or not. If yes, please turn it on.
2. Please check if the bypass AC source’s
voltage is abnormal or not. If yes, please
wait for the bypass AC source to be
restored.
3. If the alarm message still exists after the
solutions mentioned above have been
executed, please contact service personnel.
5
Bypass Input
Freq Out
Range
1. The bypass switch is
turned off.
2. The bypass AC source’s
frequency is abnormal.
1. Please check if the bypass switch is turned
off or not. If yes, please turn it on.
2. Please check if the bypass AC source’s
frequency is abnormal or not. If yes,
please wait for the bypass AC source to be
restored.
3. If the alarm message still exists after the
solutions mentioned above have been
executed, please contact service personnel.