EasyManua.ls Logo

Distech Controls ECB-VAVS - CO2 Sensor

Distech Controls ECB-VAVS
72 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
13ECB-VAVS Preloaded Applications
CO
2
Sensor
CO
2
sensor priorities are as follows:
1) Allure EC-Smart-Vue with CO
2
sensor.
2) Allure EC-Smart-Air with CO
2
sensor.
3) CO
2
sensor configured on Input 3.
The Allure EC-Smart-Vue with CO
2
sensor will have priority over the EC-Smart-Air with CO
2
sensor
and over the CO
2
sensor configured on Input 3. For example, if Input 3 is configured for a CO
2
sensor
and there is also one Allure EC-Smart-Vue with CO
2
sensor and one Allure EC-Smart-Air with CO
2
sensor, then the CO
2
Sensor (AV10) variable will only take into account the Allure EC-Smart-Vue with
CO
2
sensor.
CO
2
Control
The CO
2
is calculated by a PID loop. The PID loop is activated if CO2Sensor (AV10) variable is valid
(less or equal to 5000 ppm). In a PID configuration, the default value of the CO2Setpoint (AV52) vari-
able is 1000 ppm.
The PID output is multiplied by 2 in order to control the air flow in the first half of the PID loop (0-50%).
As for the second half of the PID loop (50-100%), the CO2Load (AV53) should be read by the AHU to
adjust the outdoor air damper. You can also use the maximum of all the PID loops to increase the min-
imum fresh air of the AHU supplying this area.
Air Flow Setpoint (AirFlowSP)
The Air Flow calculation depends on the CO
2
load:
Figure2: Air Flow Setpoint Calculation
For example, the AirFlow setpoint is directly linked to the CO2Load (AV53):
£ If CO2Load is 0% then AirFlowSetpoint is equal to MinAirFlow Sp.
£ If CO2Load is 65% then AirFlowSetpoint is equal to the following:
(((MaxFlowSp - MinFlowSp) x 0.65) + MinFlowSp)
The AirFlow setpoint will be the maximum value between the air flow setpoint based on the space
temperature and the CO
2
flow setpoint.
Sequence of Operation

Table of Contents

Related product manuals