64 ECB-VAVS Preloaded Applications
How to release overrides
The presence of the icon in the display screens of the Flow Setpoint or Damper parameters indi-
cates that either of them is overridden. An override normally times out after two hours. However, it
should be released manually when airflow balancing is complete. Also note that both the Flow Set-
point and Damper parameters cannot be overridden at the same time, so overriding one parameter
automatically releases the other. To manually release an override:
1. Press and hold both arrow keys simultaneously.
The screen displays three dashes.
2. Press the Menu button.
How to Exit the Submenu
£ Press the Menu button several times until the Exit screen appears. Then press either of the arrow
keys.
£ Press and hold the Menu button for 5 seconds.