44 ECB-VAVS Preloaded Applications
Setting up the Parameters and Calibrating the Sensor
From the Allure EC-Smart-Vue’s General Configuration submenu, the sensor’s subnet ID can be set.
In addition, other functions can be carried out such as calibrating the Allure EC-Smart-Vue’s space
temperature and humidity sensor, verifying the Device ID and adjusting the screen contrast.
This procedure also allows you to calibrate the humidity sensor if your Allure EC-Smart-Vue is equipped with this
option.
How to Enter the General Configuration Submenu
To enter the advanced menus:
1. Hold the Menu button for five seconds:
°F
pm
5 sec
The password field appears.
2. Use the arrow keys to increase or decrease the displayed number until it matches the configured
password.
Screen timeout: 15 s
By default, the password is 9995.
3. Press the Menu button to submit the password.
Screen timeout: 15 s
Upon submitting the correct password, the advanced menu is displayed.
4. Press the Menu button several times until GEN CFG appears on the display.
Press several times
5. Press either of the arrow keys to enter the General Configuration submenu.
Allure EC-Smart-Vue Screen-by-Screen Guide