Display Description
OT - Selection of type of obstacle.
00 - Overcurrent or door stopped
01 - Overcurrent
02 - Door stopped
CR - Correction to calculated speed. [mm/s]
DO NOT USE (diagnostic purposes only)
R9 - Enabling automatic closing after command 1-9
(STOP) from terminal board.
OF - Disabled.
ON - Enabled.
NO - None. Disables safety device 1-9.
SM - Selection of operating mode of device connected
to terminals 1-6.
00 -
During the operation, the opening of the safety contact
stops movement (with disengagement if → / ).
01 - During the operation, the opening of the safety con-
tact stops movement (with disengagement if →
/ ). When the contact closes again, the inter-
rupted operation continues.
02 - During the operation, the opening of the safety con-
tact stops movement (with disengagement if →
/ ). When the contact closes again, an opening
operation is performed.
03 - During the opening operation, the opening of the
safety contact stops movement (with disengagement
if → / ). When the contact closes again, the
interrupted opening operation is resumed. During the
closing operation, the safety device is ignored.
04 - During the closing operation, the opening of the
safety contact reverses the movement. During the
opening operation, the safety device is ignored.
05 -
During the closing operation, the opening of the safety
contact stops and reverses the movement. During the
opening operation, opening of the safety contact stops
movement (with disengagement if → / ).
TN - Setting of intervention temperature for NIO anti-
freeze system. [°C]
Adjustment of the working temperature of the control
panel. The value does not refer to ambient temperature.
20
TB - Display of working temperature of control panel.
DO NOT USE
WO - Setting of pre-flashing time on opening. [s]
Adjustment of the lead time for the switch-on of the
flashing light, in relation to the start of the opening
operation from a voluntary command.
00 - Minimum
05 - Maximum
00
AP - Advanced Parameters