10. Troubleshooting
Problem Possible cause Signal /
Alarm
Operation
The automation does not
open or close.
No power.
Check power supply cable.
Short-circuited accessories Disconnect all accessories
from terminals 0-1 (a voltage
of 24V= must be present) and
reconnect them one at a time.
Contact Technical Service
Blown line fuse.
Replace fuse.
Safety contacts are open.
Check that the safety contacts
are closed correctly (NC).
Safety contacts not correctly
connected or self-controlled
safety edge not functioning
correctly.
Check connections to terminals
6-8 on control panel and con-
nections to the self-controlled
safety edge.
SAFETY SWITCH release mi-
croswitch open.
Check that the hatch is closed
correctly and the microswitch
makes contact.
Photocells activated.
Check that the photocells are
clean and operating correctly.
The automatic closing does
not work.
Issue any command. If the
problem persists, contact
Technical Service
Check terminal 9 on the con-
trol panel.
Mechanical fault
Check the rack or transmis-
sion chain, and/or the me-
chanical parts.
Faulty motor
Check motor connection, if
the problem persists, contact
Technical Service.
Faulty control panel
Replace the control panel.