43
EN
IP2163EN
Type of
alarm
Display Description Operation LED
Radio
operations alarm
R3 - Storage module not detected
(with RDX inserted).
Insert a working storage module or
remove RDX.
R5 - Storage module not working (re-
gardless of RDX)
Replace the storage module.
Accessories alarm
A0 - Failure of test of safety sensor
on contact 6.
Check that device SOFA1-A2/GOPAV
is working correctly.
If the supplementary card is not in-
serted, check that
is not set to
/
A3 - Failure of test of safety sensor
on contact 8.
Check that device SOFA1-A2/GOPAV
is working correctly.
If the supplementary card is not in-
serted, check that
is not set to
/
A7 - Incorrect connection of contact
9 to G3
Check that terminal 1 and 9 are cor-
rectly connected.
A9 - Flashing light output short cir-
cuit alarm
Check that the flashing light is working
properly.
AB - Gate open indicator light
shortcircuit alarm
Check that the gate open indicator
light is working correctly.
Battery
B0 - Battery almost flat Check battery voltage.
Replace battery.
Power supply
alarm
P0 - No mains voltage. Check the control panel is powered
correctly.
Check the line fuse.
Check the mains power supply.
P1 - Microswitch voltage too low Check the control panel is powered
correctly.
Control panel
internal alarm
I2 - No communication between
parallel automations.
Check G1 (MASTER) - G3 (SLAVE)
and G3 (MASTER) - G1 (SLAVE) con-
nections.
Reset.
If the problem persists, contact
Technical Support.
I7 - Internal parameter outside lim-
its error
Reset.
If the problem persists, replace the
control panel.
I8 - Program sequence error Reset.
If the problem persists, replace the
control panel.