M3-13P Line Contactor Coil holding voltage ”LCHoldVl”
It sets the line contactor coil holding voltage applied when the line contactor is closed and 1 s of time is elapsed. It is
expressed as percentage of the M8-2 Nominal battery voltage NomBatV”” in the BDI menu.
Example:
M8-2 Nominal battery voltage NomBatVis set to 48V and the desired line contactor coil holding voltage is 24V.
The percentage to set in the M3-27T Line Contactor Coil holding voltage ”LCHoldVl” has to be 100%*24V / 48V = 50%.
If it set to 100% the full battery voltage will be applied
M3-14P Digital Output 2 pull-in voltage ”Do2PlInV
It sets the Digital Output 2 pull in voltage applied for 1s. It is expressed as percentage of the M8-2 Nominal battery
voltage NomBatV” in the BDI menu.
If it set to 100% the full battery voltage will be applied.
M3-15P Digital Output 2 hold voltage ”Do2HoldV
It sets the Digital Output 2 holding voltage applied when the line contactor is closed and 1 s of time is elapsed. It is
expressed as percentage of the “M8-2 Nominal battery voltage NomBatV”” in the BDI menu.
If it set to 100% the full battery voltage will be applied.
M3-16P Digital Output 3 pull-in voltage ”Do3PlInV
It sets the Digital Output 3 pull in voltage applied for 1s. It is expressed as percentage of the M8-2 Nominal battery
voltage NomBatV” in the BDI menu.
If it set to 100% the full battery voltage will be applied.
M3-17P Digital Output 3 hold voltage ”Do3HoldV
It sets the Digital Output 3 holding voltage applied when the line contactor is closed and 1 s of time is elapsed. It is
expressed as percentage of the M8-2 Nominal battery voltage NomBatV”” in the BDI menu.
If it set to 100% the full battery voltage will be applied.
M3-18P Driver output 2 configuration “Drv2Cfg”
This sets the configuration for Driver Output 2.
If set to 0, no function is assigned to digital output driver 2 (pin 16 in 35 way connector)
If set to 1, digital output 2 is activated if motor temperature is higher than threshold M3-21T Motor
Temperature threshold (for output driver) “MotTmpTh”” and deactivated when motor temperature gets lower
than threshold “M3-21T Motor Temperature threshold (for output driver) “MotTmpTh””- 8 °C of hysteresis.
If set to 2, digital output 2 is activated if controller temperature is higher than threshold M3-22T Controller
Temperature threshold (for output driver) “CtrTmpTh””, and deactivated when controller temperature gets
lower than threshold M3-22T Controller Temperature threshold (for output driver) “CtrTmpTh””- 8 °C of
hysteresis .
If set to 3, digital output 2 is activated if motor temperature is higher than threshold M3-21T Motor
Temperature threshold (for output driver) “MotTmpTh”OR if controller temperature is higher than threshold
M3-22T Controller Temperature threshold (for output driver) “CtrTmpTh””, while it is deactivated when motor
temperature gets lower than threshold M3-21T Motor Temperature threshold (for output driver)
“MotTmpTh””- 8 °C of hysteresis AND controller temperature gets lower than threshold M3-22T Controller
Temperature threshold (for output driver) “CtrTmpTh””- 8 °C of hysteresis.