12 | Messages/error elimination
D-ISC 100 x xx2
143
Code Message Measures
[198] [Display heater faulty] 1. Check the plug connector for the display heating
in the display module.
2. Replace the display module.
[199] [Hardware fault display module] 1. Check the wiring connection between the display
module and the CPU module.
2. Replace the display module.
Table12.4: Critical error
12.6 Messages by expansion modules (common)
For messages (code) not listed here, please use the information
from the previous Sections.
Code Message Measures
[001] [Startup (power on)] -
[002] [Startup (external reset)] -
[003] [Startup (watchdog reset)] 1. If a soft reset is desired, no further measures are
necessary.
2. In the event of multiple, unwanted resets, contact
DURAG Service.
[004] [Startup (bod reset)] 1. In the event of multiple occurrences contact
DURAG Service.
[005] [Parameter modification stored] -
[006] [Simulation/function test] -
Table12.5: Messages by expansion modules (common)
12.7 Messages by the expansion module (analogue/
digital input/output)
For messages (code) not listed here, please use the information
from the previous Sections.
Code Message Measures
Simple fault (specific)
[160] [Current limiting (15V supply voltage)] 1. Check external wiring.
2. Check the power consumption of the connected
sensors.
Critical fault (specific)