Eaton 93E MK2 - Table 3-5. Input;Output Ratings and External Wiring Requirements for the Eaton 93 E MK2 10-40 Kva

Eaton 93E MK2
96 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
UPS
Installation Plan and Unpacking
T
able
3-5. Input
/
Output
Ratings and External Wiring Requirements for
the Eaton 93E MK2 10-40
kV
A
cross-sections
Units
Rating 50/60 Hz
Basic
Unit
Rating
Refer the
IEC
62040-1
k
VA
kW
15 20 30 40 60 80
13.5 18 27 36 54 72
Input and Output
V
oltage
V
olts
400/400 400/400 400/400 400/400 400/400 400/400
A: AC Input
to UPS Rectifier (0.99 Minimum PF)
Full
load current plus battery recharge
current
(3)
Phases
Conductor Size (Phase
A, B, C )
Amps 23 31 46 61 92 123
min mm
2
6×1
6×1
6×1 16×1 16×1
25×1
max mm
2
6×1 10×1 25×1 25×1 50×1
70×1
B: AC Input to UPS
Bypass (Five Wire,
Dual-Feed)
Full Load
Current
(3)
Phases
Amps 22 29 43 58 87 115
Conductor Size (Phase
A, B, C )
C: DC
Input from External Battery (432
Vdc)
min mm
2
6×1
6×1
6×1 16×1 16×1
25×1
max mm
2
6×1 10×1 25×1 25×1 50×1
70×1
(1)
Positive,
(1)
Negative
Total
Amps 34 46 69 92 137 183
min mm
2
6×1 6×1 10×1 16×1 35×1 50×1
Conductor
Size
D: AC Output
to Critical Load (Five
Wire)
Full Load
Current
(3)
Phases
max mm
2
16×1 25×1 35×1 50×1 50×2 70×2
Amps 22 29 43 58 87 115
Conductor Size (Phase
A, B,C )
min mm
2
6×1
6×1
6×1 16×1 16×1
25×1
max mm
2
6×1 10×1 25×1 25×1 50×1
70×1
Grounding
1.0times
Neutral (N) (Mains/Load):( Non-linear load )
1.7times
Clearance
distance:
2.0mm
Backfeed protection
device
Break
time:
15s
NOTE
Callout letters
A
,
B
,
C
, and
D
map
to
Figure
5-5.
Above mentioned is recommendation of Eaton, not imperative standard. Actual suitable configuration depends on each individual
country standard and situation.
CAUTION
External
overcurrent protection
is not provided by this
product,
but is
required
by
codes.
Refer
to
table 3-5 for wiring
requirements.
If an
input/output
lockable
disconnect
is
required,
it is to
be
supplied
by the
user.
14
Eaton 93E MK2 UPS (10-40kVA, 380/400/415V) Installation and Operation