6.4.3
Transfer from Normal to
Bypass
Mode
To
transfer
the critical load to
Bypass mode:
CAUTION
In
Bypass mode,
the critical load is not
protected
from
commercial power interruptions and
abnormalities.
1.
Select
the CONTROLS symbol on the main
menu
bar. The
System
Control
screen
is
displa
y
ed.
2. If not already
selected, select
UPS on the
System
Control
screen.
3. On the UPS
System
Control
screen, select
the NORMAL BYPASS
command,
then
press
the RETURN
pushbut
ton.
All
of the UPSs
transfer
to
Bypass
mode.
The BYPASS
status
indicator is illuminated. The
power module remains on.
W
ARNING
Power
is
present
inside the UPS
cabinet.
6.4.4
Transfer from
Bypass
to Normal
Mode
To
transfer
the critical load to Normal
mode:
1.
Select
the CONTROLS symbol on the main
menu
bar. The
System
Control
screen
is
displa
y
ed.
2. If not already
selected, select
UPS on the
System
Control
screen.
3. On the UPS
System
Control
screen, select
the BYPASS NORMAL
command,
then
press
the RETURN
pushbut
ton.
All
of the UPSs
transfer
to Normal
mode.
If the
power module
is not available, the
system remains on
bypass
and an alarm
sounds.
The NORMAL
status
indicator is
illuminated.
W
ARNING
Power
is
present
inside the UPS
cabinet.
69
Eaton 93E MK2 UPS (10-40kVA, 380/400/415V) Installation and Operation