UPS
Installation Plan and Unpacking
surfaces
only
.
•
The
UPS operating temperature at ambient 0-40°C
.
•
The
battery operating temperature at ambient 20-25°C
.
•
Relative humidity at 95%, non-condensing
•
The
system must
be installed in a
temperature
and humidity
controlled
indoor area free
of
conductiv
e
contaminants.
•
The
system If the UPS is to operate at altitude higher than 1000m (3300ft),
contact an Eaton service representative for further important information on
operating on higher altitude.
Failure to follow
guidelines
may void your
w
ar
rant
y
.
The UPS
equipment operating environment must meet
the
weight requirements shown in
Table 3-1 and
the
size
requirements shown
in Figure 3-1
through
Figure 3-5.
Dimensions
are in
millimetres (inc
hes).
T
able
3-1. UPS Cabinet
Weights
Model
Weight (
kg
)
Net Weight
Gross Weight
Descriptions
93E MK2-10I-9Ah-MBS
770
859
93E MK2-15I-9Ah-MBS
770
859
93E MK2-20I-9Ah-MBS
770
859
93E MK2-30I-9Ah-MBS
780
869
93E MK2-40I-9Ah-MBS
790
879
I- Internal battery
MBS-with internal
MBS
The UPS
cabinet uses
forced air cooling to
regulate
internal
component temperature.
Air
inlets are in the
front
of the
cabinet
and
outlets
are in the back of the
cabinet.
Allow
clearance
in front of and in back of the
cabinet
for proper air
circulation. The
clearances required
around the UPS
cabinet
are
shown in
Table
3-2 and Table 3-3
T
able
3-2. UPS Cabinet
Clearances
From Top of
Cabinet
At least 300 mm (12") working
space
From Front of
Cabinet
At least 900 mm (36") working
space
From
Back of
Cabinet
At least 600 mm (36") working
space
From Right
Side
of
Cabinet
See Table No:
3-3
From Left
Side
of
Cabinet
See Table No:
3-3