8.2
Performing Preventative
Maintenance
The UPS
system requires
very little
preventative maintenance. However,
the
system
should be
inspected
periodically to verify that the units are
operating
normally and that the
batteries
are in good
condition.
8.2.1
DAILY
Maintenance
Perform
the following
steps
daily:
1. Check the area
surrounding
the UPS
system. Ensure
the area is not
cluttered,
allowing free
access
to
the
unit.
2.
Ensure
the air
intakes
(vents on the front door of the UPS
cabinet
and the
exhaust openings
(on the rear
of
the UPS cabinet) are not
bloc
k
ed.
3.
Ensure
the
operating environment
is within the
parameters specified
in
paragraph
3.2.1 and
Chapter 9,
“Product
Specifications
.
4.
Ensure
the UPS is in Normal
mode
(Normal
status
indicator is illuminated). If an alarm lamp is
illuminated
or the Normal
status
indicator is not illuminated,
contact
an Eaton
service
represent
ativ
e.
8.2.2
MONTHLY
Maintenance
Perform
the following
steps monthly:
1. Monitor
system parameters
as
described
in
paragraph
6.2, “Using the Control
P
anel
.
2. Check the UPS air filters (located behind the front door) and
wash
or
replace
as
necessary.
See Figure
8-1
for filter location.
Contact
an Eaton
service representative
for
replacement
filters. To
remove
the
filters:
CAUTION
Verify
washed
filter is
thoroughly
dry
before reinst
alling
.
a.
Unfasten
the front door by lifting the latch from the
bottom
and turning to the right
(countercloc
kwise)
and swing the door open (see
Figure
6-1).
b.
Remove
the upper and lower foam filters from the frame on the front
door
.
c.
Replace
the
washed
or new foam filters into the frame on the front
door
.
d. Close the front door and
secure
the
latc
h.
3. Record
maintenance results
and any
corrective actions
in a
suitable
log
.
78
Eaton 93E MK2 UPS (10-40kVA, 380/400/415V) Installation and Operation