6.4.1
Starting the Parallel UPS in Standard Normal Mode (Default
Mode)
To start the UPS
sy
stem:
1.
Unfasten
the front door by lifting the latch from the
bottom
and turning to the right
(counterclockwise)
and
swing the door open (see Figure
6-1).
2. Verify that all input
breakers
are
open.
3. Verify that the
maintenance bypass breakers
are
open.
4. Close all Module
Output Breakers (MOBs).
5. Close all UPS input
feeder
circuit
break
ers.
6. If the UPSs are wired for dual input, close all of the UPSs
Bypass
input
feeder
circuit
break
ers.
7. Close all input
break
ers.
8. If the UPSs are wired for dual input, close all
bypass
input
switc
hes.
9. Make sure MBS cover is
inst
alled.
10. Close the door and
secure
the
latc
h.
11. Close all
external battery break
ers.
12.
Observe
the UPS control panel display
becoming
active, indicating logic
po
w
er
.
13. Verify no alarms are
activ
e.
14.
Select
the CONTROLS symbol on the main
menu
bar. The
System
Control
screen
is
displa
y
ed.
15. If not already
selected, select
UPS on the
System
Control
screen.
16. On the UPS
System
Control
screen, select
the LOAD OFF NORMAL
command,
then
press the
RETURN
pushbut
ton.
17. If
requested, enter
the Level 1
password.
Default
password
is
1111.
After
entering password,
UPS will
transfer
to
bypass
first and the
Bypass
LED
will
illuminate.
All
rectifiers
and
inverters
turn on. The
inverters continue
to ramp
up to full v
olt
age.
Once all
inverters
reach full voltage, the UPS
output contactor closes
and the static
switch
turns off.
P
o
w
er
is now
supplied
to the critical load in
Standard
Normal
mode.
It
takes
approximately
one
minute
for
the
UPS
to
achieve Standard
Normal
mode.
The Normal
status
indicator is
illuminated.
Eaton 93E MK2 UPS (10-40kVA, 380/400/415V) Installation and Operation