W
ARNING
Power
is
present
inside the UPS
cabinet.
6.3.4
Transfer from
Bypass
to Normal
Mode
To
transfer
the critical load to Normal
mode:
1.
Select
the CONTROLS symbol on the main
menu
bar. The
System
Control
screen
is
displa
y
ed.
2. If not already
selected, select
UPS on the
System
Control
screen.
3. On the UPS
System
Control
screen, select
the BYPASS NORMAL
command,
then
press
the RETURN
pushbut
ton.
The UPS
transfers
to Normal
mode.
If the
power module
is not available, the
system remains
on
b
ypass
and an alarm
sounds.
The NORMAL
status
indicator is
illuminated.
6.3.5
Transfer from Standard Normal Mode to
HE
mode
To
transfer
the load to HE
mode:
1.
Select
the CONTROLS symbol on the main
menu
bar. The
System
Control
screen
is
displa
y
ed.
2. If not already
selected, select
UPS on the
System
Control
screen.
3. On the UPS
System
Control
screen, select
the HE: DISABLE
ENABLE
command,
then
press the
RETURN
pushbut
ton.
After
battery
is fully
charged,
the UPS
transfers
to HE
mode
if no
abnormal power conditions
are
detected.
If
abnormal power conditions
are
detected,
the UPS will wait and
transfer
to HE
mode when conditions
are
cleared.
The NORMAL
status
indicator is
illuminated.
6.3.6
Transfer from
HE
Mode to Standard Normal
Mode
To
transfer
the load to
Standard
Normal
mode:
1.
Select
the CONTROLS symbol on the main
menu
bar. The
System
Control
screen
is
displa
y
ed.
2. If not already
selected, select
UPS on the
System
Control
screen.
3. On the UPS
System
Control
screen, select
the HE: ENABLE
DISABLE
command,
then
press the
RETURN
pushbut
ton.
The UPS
transfers
to
Standard
Normal
mode.
The NORMAL
status
indicator is
illuminated.
Eaton 93E MK2 UPS (10-40kVA, 380/400/415V) Installation and Operation