Installation Plan and Unpacking
3.2.3
UPS System Interface Wiring
Preparation
Control wiring for
features
and
options
should be
connected
at the
customer interface
terminal blocks
located
inside the
UPS
.
W
ARNING
Do not directly
connect contactor contacts
to the mains
related
circuits.
Reinforced
insulation
is
required before connecting
to the
mains.
Read and
understand
the following
notes
while planning and
performing
the
inst
allation:
Interface
wiring should be rated for 24V, 1A
minimum.
For
interface
wiring from 30V to 600V, the wire should be rated for 600V, 1A
minimum.
Because
of the REPO and building alarm wiring route in the UPS
cabinet,
the wire should be rated for
a
minimum
of
300
V
.
Use
twisted-pair
wires for each input and return or
common.
All
interface
wiring and conduit is to be
supplied
by the
customer
.
When installing
external interface
wiring
between
a REPO or building alarm and the UPS
interface terminals,
conduit
must
be installed
between
each device and the UPS
cabinet.
If using the
power
terminal wiring
channel,
keep
interface
wiring
separate
from
power
wiring or use
shielded
wire.
If using conduit, install the
interface
wiring in
separate
conduit from the
power
wiring
.
All
building alarm inputs require an
isolated normally-open contact
or
switch
(rated at 24 Vdc, 20
mA
minimum)
connected between
the alarm input and
common
terminal.
All
control wiring and
switch cont
acts
are
customer-supplied.
LAN
and
telephone
drops for use with Mini-Slot
connectivity
cards
must
be
supplied
by the
customer
.
The REPO
feature opens
all
contactors
in the UPS
cabinet
and
isolates power
from your critical load.
Local
electrical
codes
may also require tripping
upstream protective devices
to the
UPS
.
The REPO
switch must
be a
latching-type switch
not tied to any other
circuits.
A jumper wire
must
be
connected between
pins 3 and 4 on the REPO terminal block if using a
normally-
closed
REPO
switc
h.
REPO wiring should be a
minimum
of
0.5~2.0
mm
2
.
The REPO
switch
wiring
must
be in
accordance
with local
regulations.
The
maximum distance between
the REPO and the UPS
cannot exceed
150
metres
(500 f
eet).
18
Eaton 93E MK2 UPS (10-40kVA, 380/400/415V) Installation and Operation