6.4.5
Single
UPS
Shutdown
To shut down the
UPS:
1. Open the MOB for the UPS being shut
do
wn.
2.
Select
the CONTROLS symbol on the main
menu
bar. The
System
Control
screen
is
displa
y
ed.
3. If not already
selected, select
UPS on the
System
Control
screen.
4. On the UPS
System
Control
screen, select
the NORMAL UPS OFF
command,
then
press
the RETURN
pushbut
ton.
The
output
and
bypass backfeed
relay
open,
and the
power module
is
turned
off on the UPS being
shut
do
wn.
Logic
power remains on.
W
ARNING
Power
is
present
inside the UPS
cabinet
until the
upstream
input
feeder
circuit
breaker
is
opened.
5. Open the UPS input and the
bypass feeder
circuit
breakers
for the UPS being shut
do
wn.
6. If EBCs are installed, open all
battery break
ers
The UPS is now
completely
shut
do
wn.
6.4.6
Single
UPS
Restart
To
restart
a single UPS from a
shutdown
st
ate:
1. Close the MOB for the UPS being
rest
arted.
2. Close the UPS input and
bypass feeder
circuit
breakers
for the UPS being
rest
arted.
3. Close the input
switc
h.
4. If the UPSs are wired for dual input, close the
bypass
input
switc
h.
5. Close the
output switc
h.
6. Close the
external battery break
ers.
7. On the UPS being
restarted, observe
the UPS control panel display
becoming
active, indicating
logic
p
owe
r
.
8. Verify no alarms are active on the UPS being
rest
arted.
9. On the UPS being
restarted, select
the CONTROLS symbol on the main
menu
bar. The
System Control
screen
is
displa
y
ed.
10. If not already
selected, select
UPS on the
System
Control
screen.
11. On the UPS
System
Control
screen, select
the UPS OFF NORMAL
command,
then
press
the RETURN
pushbut
ton.
12. If
requested, enter
the Level 1
password.
Default
password
is
1111.
The rectifier and inverter turn on. The inverter
continues
to ramp up to full v
olt
age.
Once the inverter
reaches
full voltage, the UPS
output contactor closes
and the static
switch
turns
of
f
.
Power
is now
supplied
to the critical load in
Standard
Normal
mode
along with the other UPSs online. It
takes approximately
one
minute
for the UPS to
achieve Standard
Normal
mode.
The Normal
status
indicator is
illuminated.
Eaton 93E MK2 UPS (10-40kVA, 380/400/415V) Installation and Operation