Specifications
Overload Capability
9.2.2
UPS
Input
T
able
9-3. UPS Input Rating
Operating Input
V
oltage
380/400/415
V
ac
190/330–276/478V
(-15%, +20%)
at
100%
load
Input
V
oltage Range
116/201-276/478V (-50%, +20%)
at
50%
load
Operating Input Frequency
Range
50/60 Hz
Input Frequency
Range
40-72Hz
See Table 3-5.
Operating Input Current
Adjustable
Input Current Harmonic
Content
5% THD
at
full
load
Power
Factor
Minimum
0.99
Line
Surges
6 kV OC, 3 kA SC per
ANSI 62.41 and
IEC 801
4
Battery
V
oltage
432 Vdc
Internal
Battery Charging Capacity (432
Vdc)
5.3A maximum
at
any load up to100% load for 10
kVA
UPS
5.3A maximum
at
any load up to100% load for 15
kVA
UPS
5.3 A maximum
at
any load up to100% load for 20
kVA
UPS
8A maximum
at
any load up to100% load for 30
kVA
UPS
10.6A maximum
at
any load up to100% load for 40
kVA
UPS
9.2.3
UPS
Output
T
able
9-4. UPS Output Rating
UPS Output
Capacity
100% rated
current
Output
V
oltage Regulation
± 1% (10% to 100%
load)
Nominal Output
V
oltage
380 Vac, 400 Vac and 415 Vac
nominal
2% maximum
THD
(linear load)
Output
V
oltage
Harmonic Content
5% maximum
THD
(nonlinear
load)
Output
Current
See Table
3-5.
Output
V
oltage Balance
<
2% for 100% maximum load imbalance (linear
load)
Output
V
oltage Phase Displacement
<
2.5° for 100% maximum load imbalance (linear
load)
Frequency
Regulation
0.1 Hz free
running
Synchronous to
Bypass
± 4 Hz
(default
setting)
Frequency
Slew Rate
3 Hz
per second (default
setting)
Load
Compatibility
0.9 PF
Leading
0.7 PF
Lagging
110%
for 60
minutes
125%
for 10
minutes
150
% for
1 minutes
150%
for 500
milliseconds
82
Eaton 93E MK2 UPS (10-40kVA, 380/400/415V) Installation and Operation