Loading...
To use the REPO
switc
h:
1. Firmly push the red
pushbutton
until it locks into place. The
switch latches
into the
activated
st
ate.
The input,
output, battery,
and
bypass backfeed contactors open,
and the
power module
is
turned
of
f
immediately, without
asking for v
erification.
CAUTION
Do not
attempt
to
restart
the
system
after the REPO until the
cause
of the
shutdown
has
been
identified and
cleared.
2. To
deactivate
the REPO
switch
in
preparation
for
restarting
the UPS, insert the
supplied
key and
rot
ate
clockwise
until the red
pushbutton
releases.
To
remove
the key,
rotate
the key back to the vertical
position.
3.
Restart
the UPS by following the
procedure
in
paragraph
6.3.1 or
6.3.2.