04/10 MN04020001Z-EN
Introduction
65
51 External fault Error message at a digital input (DI1 - DI6),
programmed as input for an external error
message.
Check the programming (P3.5, P3.6) and check the
device indicated by the error message.
Check the cabling for the respective device as well.
53 Field bus error The communication link between the master
device and the drive's field bus has been inter-
rupted.
Check the installation.
Further notes are provided in the manual of the optional
fieldbus interface (CANopen, PROFIBUS DP etc.)
If the installation is OK, please contact your closest
Moeller representative.
54
Fieldbus interface
error
MMX-NET-XA mounting frame for fieldbus
interface cards is not connected to the
frequency inverter.
Optional fieldbus interface is not fitted.
Error message with activated fieldbus connection of the
interface between the frequency inverter and the
mounting frame (MMX-NET-XA).
Error message as per P8.15.
Further notes are provided in the manual of the optional
fieldbus interface (CANopen, PROFIBUS DP etc.)
55
Thermistor Overtemperature in the motor.
Connection to the thermistor, temperature
switch or thermo click is interrupted.
Error message as per P8.11.
Display
Designation Possible cause Instructions

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Eaton MMX34AA9D0 Series and is the answer not in the manual?

Eaton MMX34AA9D0 Series Specifications

General IconGeneral
BrandEaton
ModelMMX34AA9D0 Series
CategoryDC Drives
LanguageEnglish

Related product manuals