14. ERROR/WARNING TABLES
14.1 ERROR DEFINITIONS AND TROUBLESHOOTING
CODE
DESCRIPTION
TROUBLESHOOTING
E000
Internal Communication Fault
Restart inverter. If error persists, contact the
E002
Bat On Mos Fail
Restart inverter. If error persists, contact the
distributor
E003
CT Fail
Restart inverter, if the error persists, contact the
distributor
E008
CAN communication error in parallel
system
Ensure CAN paralleling cables are connected to
proper ports between inverters
E009
No master in parallel system
Check parallel setting for Master/Slave to ensure
there is only one Master set
E012
UPS output short circuit
Check if the load has a short circuit. If not, turn
loads o and reset the system
E013
UPS reserve current
Restart the inverter. If error persists, contact the
distributor
E016
Relay fault
Restart inverter. If error persists, contact the
E017
Internal communication fault 2
Restart inverter. If error persists, contact the
E018
Internal communication fault 3
Restart inverter. If error persists, contact the
E019
Bus voltage too high Check if PV input voltage is >480VDC
E020
EPS connection fault
Check if Inverter and AC connection is installed
correctly
E021
PV voltage too high Check if PV input voltage is >480VDC
E022
Over current internal
Restart inverter. If error persists, contact the
E024
PV short Check PV connections for short circuit
E025
Temperature too high
The internal temperature of the is too high. Turn
the inverter o for 10+ minutes and restart the
system. If error persists, please contact the
E026
Internal Fault
Restart inverter. If error persists, contact the
distributor
E028
Sync signal lost in parallel system
Ensure CAN paralleling cables are connected to
proper ports between inverters
E029
Sync trigger signal lost in parallel
system
Ensure CAN paralleling cables are connected to
proper ports between inverters
E031
Internal communication fault 4
Restart inverter. If error persists, contact the
distributor