Operating manual - Fan CF-C Mounting, installation and connection
2004930 10.19/0.2 www.elektror.com 43 of 84
EN
2 Electrical test - A general visual inspection of the condition of electrical
connections and wires should be carried out. In the event of
damage and installation defects, restore them to the appropriate
condition.
- Check the conformity of the electrical connection parameters with
the values stated on the nameplate.
- Check the proper execution of earth connections and equipotential
bonding.
- Check the correct status of the neutral wire.
- Check the fastening of cables and terminals.
- Check that all existing junction boxes and cable ducts are closed
and that the cables are connected.
- Check the rotation direction of the electric motor to see if it matches
the arrow.
- Check earthing lugs connections, if present.
3 Testing of monitoring
and auxiliary
equipment
- Check the connected devices that monitor the fan operation in
order to confirm their proper operation.
- Check the connections and wiring of the monitoring and auxiliary
equipment.
- Check the installation and operational status of safety systems and
protective devices.
- According to the drawings, check the stationary and mobile safety
systems to confirm their correct operation.
6.7.1 Checking the gap
Before first starting the fan, check the radial gap between the intake nozzle or inlet cone and
the impeller and note its width.
Transporting the fan to its destination site does not exclude the possibility of moving the inlet
side cone in relation to the impeller. The minimum size of this gap is a prerequisite for safe fan
operation.