246 Affinity User Guide
www.controltechniques.com Issue Number: 5
Table 12-41 Size 4 (690V) emission compliance
Table 12-42 Size 5 (400V) emission compliance
Table 12-43 Size 5 (690V) emission compliance
Table 12-44 Size 6 (400V only) emission compliance
*Refer to section 12.1.20 Maximum motor cable lengths on page 243.
Table 12-45 Size 6 (690V only) emission compliance
*Refer to section 12.1.20 Maximum motor cable lengths on page 243.
Key (shown in decreasing order of permitted emission level):
E2R EN 61800-3:2004 second environment, restricted distribution
(Additional measures may be required to prevent interference)
E2U EN 61800-3:2004 second environment, unrestricted distribution
I Industrial generic standard EN 61000-6-4:2007
EN 61800-3:2004 first environment restricted distribution (The
following caution is required by EN 61800-3:2004)
R Residential generic standard EN 61000-6-3:2007
EN 61800-3:2004 first environment unrestricted distribution
EN 61800-3:2004 defines the following:
• The first environment is one that includes residential premises. It
also includes establishments directly connected without intermediate
transformers to a low-voltage power supply network which supplies
buildings used for residential purposes.
• The second environment is one that includes all establishments
other than those directly connected to a low-voltage power supply
network which supplies buildings used for residential purposes.
• Restricted distribution is defined as a mode of sales distribution in
which the manufacturer restricts the supply of equipment to
suppliers, customers or users who separately or jointly have
technical competence in the EMC requirements of the application of
drives.
12.2 Optional external EMC filters
Table 12-46 EMC filter cross reference
Table 12-47 IP54 EMC filter cross reference
Motor cable length
(m)
Switching frequency (kHz)
3468
Using internal filter:
Any E2R
Using external filter:
0 to 25 I
25 to 50 I E2U
50 to 75 I E2U
75 to 100 I E2U
Motor cable
length (m)
Switching frequency (kHz)
3468
Using internal filter:
100 E2U
Using external filter:
0 to 100 I
Motor cable
length (m)
Switching frequency (kHz)
3468
Using internal filter:
100 E2R
Using external filter:
0 to 25 I
0 to 100 I Do not use
Motor cable
length (m)
Switching frequency (kHz)
346
Using internal filter:
0 to 100 E2U
100 to max* E2R
Using external filter:
0 to 100 I
Motor cable
length (m)
Switching frequency (kHz)
346
Using internal filter:
0 to 100 E2U
100 to max* E2R
Using external filter:
0 to 25 I
0 to 100 I Do not use
This is a product of the restricted distribution class according
to IEC 61800-3. In a residential environment this product may
cause radio interference in which case the user may be
required to take adequate measures.
Drive
Schaffner Epcos
CT part no. CT part no.
BA1201 to BA1202 4200-6118 4200-6121
BA1203 to BA1204 4200-6119 4200-6120
BA2201 to BA2203 4200-6210 4200-6211
BA3201 to BA3202 4200-6307 4200-6306
BA4201 to BA4203 4200-6406 4200-6405
BA5201 to BA5202 4200-6503 4200-6501
BA1401 to BA1404 4200-6118 4200-6121
BA1405 to BA1406 4200-6119 4200-6120
BA2401 to BA2403 4200-6210 4200-6211
BA3401 to BA3403 4200-6305 4200-6306
BA4401 to BA4403 4200-6406 4200-6405
BA5401 to BA5402 4200-6503 4200-6501
BA6401 to BA6402 4200-6603 4200-6601
BA3501 to BA3507 4200-6309 4200-6308
BA4601 to BA4606 4200-6408 4200-6407
BA5601 to BA5602 4200-6504 4200-6502
BA6601 to BA6602 4200-6604 4200-6602
Drive CT Part number
BA1201 to BA1202 4200-6125
BA1203 to BA1204 4200-6124
BA1401 to BA1404 4200-6125
BA1405 to BA1406 4200-6124
BA2201 to BA2203 4200-6218
BA2401 to BA2403 4200-6218
BA3201 to BA3202 4200-6319
BA3401 to BA3403 4200-6318
BA3501 to BA3502 4200-6320