Figure 11-38 SM-I/O 24V Protected analog output logic diagram
SM-I/O 24V Protected parameters
0.XX
0.XX
Key
Read-write (RW)
parameter
Read-only (RO)
parameter
Input
terminals
Output
terminals
The parameters are all shown at their default settings
T12 Analog output 2
T10 Analog output 1
10
Parameter
Range(
Ú) Default(Ö)
Type
x.01 Solutions Module ID 0 to 599 205 RO Uni PT US
x.02
Solutions Module Main Software Version
0.00 to 99.99 RO Uni NC PT
x.03 T5 digital I/O 3 state
OFF (0) or On (1)
RO Bit NC PT
x.04 T6 digital I/O 4 state RO Bit NC PT
x.05 T7 digital input 5 state RO Bit NC PT
x.06 T8 digital input 6 state RO Bit NC PT
x.07 T9 digital input 7 state RO Bit NC PT
x.08 Relay 1 state RO Bit NC PT
x.09 T3 digital I/O 1 state RO Bit NC PT
x.10 T4 digital I/O 2 state RO Bit NC PT
x.11 T3 digital I/O 1 invert
OFF (0)
RW Bit US
x.12 T4 digital I/O 2 invert RW Bit US
x.13 T5 digital I/O 3 invert RW Bit US
x.14 T6 digital I/O 4 invert RW Bit US
x.15
T7 digital input 5 invert
RW Bit US
x.16
T8 digital input 6 invert
RW Bit US
x.17
T9 digital input 7 invert
RW Bit US
x.18 Relay 1 invert RW Bit US
x.20 Digital I/O read word 0 to 255
RO Uni NC PT
x.21 T3 digital I/O 1 source/destination
Pr 0.00 to Pr 50.99 Pr 0.00
RW Uni DE US
x.22 T4 digital I/O 2 source/destination RW Uni DE US
x.23 T5 digital I/O 3 source/destination RW Uni DE US
x.24 T6 digital I/O 4 source/destination RW Uni DE US
x.25 T7 digital input 5 destination RW Uni DE US
x.26 T8 digital input 6 destination RW Uni DE US
x.27 T9 digital input 7 destination RW Uni DE US
x.28 Relay 1 source RW Uni US
x.29 T6 digital I/O 4 output select
OFF (0) or On (1)
On (1) RW Bit US
x.31 T3 digital I/O 1 output select
OFF (0)
RW Bit US
x.32 T4 digital I/O 2 output select RW Bit US
x.33 T5 digital I/O 3 output select RW Bit US
x.39 Analog output mode
0-20, 20-0, 4-20, 20-4
0-20 RW Uni US
x.40 Relay 2 state 0.0 or 100.0 %
RO Bit NC PT
x.42 Relay 2 invert OFF (0) or On (1) OFF (0) RW Bit US
x.43 Relay 2 source Pr 0.00 to Pr 50.99 Pr 0.00 RW Uni US
x.45 Analog output 2 scaling 0.000 to 4.000 1.000 RW Uni US
x.47 Analog output 2 source
Pr 0.00 to Pr 50.99 Pr 0.00
RW Uni US
x.48 Analog output 1 source RW Uni US
x.49 Analog output 1 scaling 0.000 to 4.000 1.000 RW Uni US
x.50 Solutions Module error status 0 to 255
RO Uni NC PT
x.51
Solutions Module software sub-version
0 to 99 RO Uni NC PT