User Instructions
MAN-02-04-60-0350-EN Rev. 3 February 2019
48
Section 7: Parameter Menu
Parameter Menu
Table 15. Binary Outputs Parameter Group (3)
Menu
Item
Sub Menu
Item
Poss. Setting Notes / Comments
P10.1
Binary
Output
Output 1
47: Pos.=Int2
Position = Intermediate position 2. The width of the
interval is set with the parameter P8.6
48: Pos.=Int3
Position = Intermediate position 3. The width of the
interval is set with the parameter P8.6
49: Pos.=Int4
Position = Intermediate position 4.The width of the
interval is set with the parameter P8.6
50:
Pos.=EmergPos
Position = emergency position. The width of the interval
is set with the parameter P8.6
51: Bus Bit 1
In existing bus interface (hardware option) the output is
set according to the selected bit bus.
4)
52: Bus Bit 2
53: Bus Bit 3
54: Bus Bit 4
55: Bus Bit 5
56: Bus Bit 6
57: Bus Bit 7
58: Bus Bit 8
59: Virtual 1
Congurable output function
60: Virtual 2
61: Virtual 3
62: Virtual 4
63: Line voltage OK Supply voltage for the motor is OK
64: Control
voltage OK
The auxiliary voltage for the SMARTCON control is OK.
This function is only available if the auxiliary voltage
output is not switched on (P6.5 to 0)
65: Oil
pressure OK
The oil pressure is higher than the minimum pressure (P6.10)
66: Oil level OK The oil level is OK
67: Pump OK
The temperature sensor in the pump motor and the
external motor protection have not tripped
4-5
P10.2
Output
conf. 1
normal
Output 1 is set to normal, i.e. if the condition in point
P10.1 is met, Output 1 is set to HIGH (active HIGH)
inverted
if the condition in point P10.1 is met, Output 1 is set to
LOW (active LOW)
norm. ashing
if the condition in point P10.1 is met, Output 1 starts
blinking (active HIGH)
inv. ashing
if the condition in point P10.1 is not met, Output 1 starts
blinking (otherwise it is set to HIGH)
P10.3 Output 2 see Output 1 ---
P10.4 Output 2 Konf. see Output 1 conf. ---
P10.5 Output 3 see Output 1 ---
P10.6 Output 3 Konf. see Output 1 conf. ---
P10.7 Output 4 see Output 1 ---
P10.8 Output 4 Konf. see Output 1 conf. ---
P10.9 Output 5 see Output 1 ---
P10.10 Output 5 Konf. see Output 1 conf. ---
P10.11 Output 6 see Output 1 ---
P10.12 Output 6 Konf. see Output 1 conf. ---
P10.13 Output 7 see Output 1 ---
P10.14 Output 7 Konf. see Output 1 conf. ---
P10.15 Output 8 see Output 1 ---
P10.16 Output 8 Konf. see Output 1 conf. ---
4)
from Firmware 1.323

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Emerson Bettis RTS CL Series and is the answer not in the manual?

Emerson Bettis RTS CL Series Specifications

General IconGeneral
BrandEmerson
ModelBettis RTS CL Series
CategoryController
LanguageEnglish

Related product manuals