EasyManua.ls Logo

Emerson PACSystems Versamax - Configuration Data

Emerson PACSystems Versamax
129 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
PACSystems VersaMax Genius Network Interface User Manual Section 5
GFK-1535D Jan 2023
Configuration 87
Fault Bytes 6 and 7
Fault bytes 6 and 7 (datagram bytes 5 and 6) are automatically
interpreted by PACSystems RX7i controllers, Series 90-70 PLCs, and. They
are not relevant to other types of hosts.
Figure 63: Fault Bytes 6 and 7
5.5 Configuration Data
Datagrams can be used to read and write configuration data for an I/O
Station. However, most systems will use programmer configuration or
autoconfiguration.
For a Network Interface Unit, the configuration data specifies the rack
and slot number of a specific module in the station. The length specified
must exactly match the length of the configuration data for the module
(Network Interface Unit or another module in the I/O station); partial
configuration data cannot be read or written. For programming
instructions, you should refer to the documentation set for the PLC.
Configuration files for conventional I/O modules can be read or written
one module per message. However, the configuration files of intelligent
modules may exceed the 128-byte maximum length of a Genius
message. Therefore, any Write Configuration to an intelligent module
must be contained within a Begin/End Packet Sequence.
Multiple byte fields in datagrams are transmitted in little-endian format.
In this format, the least significant byte of a word is stored in the lowest
memory location or transmitted first in time. The most significant byte
follows.

Table of Contents

Other manuals for Emerson PACSystems Versamax

Related product manuals