Table 7-4: Measurement Status (continued)
Message Description Action
Sim mode 0 active The simulation mode is active. The given
measurements are simulated.
Turn off the simulation mode.
Advanced Simulation Mode
active
The advanced simulation mode is active. To turn off the Advanced Simulation
mode, set Holding Register 3600=0 (see
View/edit holding registers).
Invalid Lower Volume Value The given lower volume value is invalid. Check Lower Volume Status for details.
Invalid Upper Volume Value The given upper volume value is invalid. Check Upper Volume Status for details.
Using probe end projection
measurement
The probe end projection is active in the
transmitter software.
No action needed.
Reference echo present An echo has been detected in the
reference zone.
No action needed.
Sudden level jump detected This may result from various
measurement problems, such as:
• Rapid level changes
• Surface level within Blind Zone
• Disturbing echo
Check the tank to find out what causes
problem to track the surface.
• Set the Rapid Level Changes
parameter, see Rapid level changes.
• In the Blind Zones, the level may jump
to Full Tank/End of Probe
• See Disturbance echo handling.
Nearzone echo present An echo has been detected in the
nearzone.
No action needed.
Nonlinear gain used The nonlinear gain is enabled. No action needed.
Nearzone measurement The current sweep can be used as a
measurement of the nearzone.
No action needed.
7.2.5 Interface status
Interface status messages that may appear on the Integral Display, on the handheld
communicator, in DeltaV, or in Rosemount Radar Master are shown in Table 7-5:
Table 7-5: Interface Status
Message Description Action
Interface not OK The interface measurement is not OK. Check other interface status messages
for reason.
Interface not found No interface available No action needed.
Interface threshold to high Adjust Interface threshold, see Example
2: Interface peak not found.
Can't measure interface on
horizontal probe
Interface cannot be measured when the
probe is horizontally mounted.
Change the probe mounting or turn off
interface measurement by changing the
measurement mode.