Appendix H: Resource block
November 2014
Resource Block
SHED_ROUT 27 640000 Time duration at which to give up on computer writes
to function block ROut locations. Shed from ROut shall
never happen when SHED_ROUT = 0
FAULT_STATE 28 0x01(Clear) Condition set by loss of communication to an output
block, fault promoted to an output block or physical
contact. When FAIL_SAFE condition is set, then output
function blocks will perform their FAIL_SAFE actions.
SET_FSTATE 29 0x01(OFF) Allows the FAIL_SAFE condition to be manually
initiated by selecting Set.
CLR_FSTATE 30 0x01(Off) Writing a Clear to this parameter will clear the device
FAIL_SAFE if the field condition has cleared.
MAX_NOTIFY 31 3 Maximum number of unconfirmed notify messages
possible.
LIM_NOTIFY 32 3 Maximum number of unconfirmed alert notify
messages allowed.
CONFIRM_TIME 33 640000 The time the resource will wait for confirmation of
receipt of a report before trying again. Retry will not
happen when CONFIRM_TIME=0.
WRITE_LOCK 34 0x01(Not Locked) If set, no writes from anywhere are allowed, except to
clear WRITE_LOCK. Block inputs will continue to be
updated.
UPDATE_EVT 35 This alert is generated by any change to the static data.
BLOCK_ALM 36 The block alarm is used for all configuration, hardware,
connection failure, or system problems in the block.
The cause of the alert is entered in the subcode field.
The first alert to become active will set the Active
status in the Status parameter. As soon as the
Unreported status is cleared by the alert reporting
task, another block alert may be reported without
clearing the Active status, if the subcode has changed.
ALARM_SUM 37 The current alert status, unacknowledged states,
unreported states, and disabled states of the alarms
associated with the function block.
ACK_OPTION 38 0x0000(0x0000) Selection of whether alarms associated with the
function block will be automatically acknowledged.
WRITE_PRI 39 0 Priority of the alarm generated by clearing the write
lock.
WRITE_ALM 40
0X00(Uninitialized)
0x00(Uninitialized)
01/01/72 00:00:00
0x0000(Other)
0x00(State 0)
This alert is generated if the write lock parameter is
cleared. Five sub-elements available:
- UNACKNOWLEDGED
- ALARM_STATE
- TIME_STAMP
- SUB_CODE
- VALUE
ITK_VER 41 5 Major revision number of the inter operability test case
used in certifying this device as interoperable. The
format and range are controlled by the Fieldbus
Foundation.
distributor 42 0x00001151
(Rosemount)
Reserved for use as distributor ID. No F
OUNDATION
enumerations defined at this time.
DEV_STRING 43 0 This is used to load new licensing into the device. The
value can be written but will always read back with a
value of 0.
XD_OPTIONS 44 0x00000000
(0x00000000)
Indicates which transducer block licensing options are
enabled.
Parameter
Index
number
Default value Description