Description of parameters (ToF Tool) Cerabar S/Deltabar S
124 Endress+Hauser
ZERO POSITION
Entry
Enter value for level offset.
If the measurement should not start at the mounting location of the device, e.g. for
containers with a sump, carry out zero point shift (level offset).
Prerequisite:
• CALIBRATION MODE = dry
P01-PMP75xxx-19-xx-xx-xx-001
Fig. 28: Zero point shift
1 Device is mounted above the level lower range value: a positive value has to be
entered for ZERO POSITION.
2 Device is mounted below the level lower range value: a negative value has to be
entered for ZERO POSITION.
Factory setting:
0.0
DAMPING VALUE
Entry
Enter damping time (time constant τ).
The damping affects the speed at which all subsequent elements, such as the on-site
display, measured value and OUT value of the Analog Input Block react to a change in the
pressure.
Input range:
0.0...999.0 s
Factory setting:
2.0 s or as per order specifications
ToF Tool, Table 9: OPERATING MENU → SETTINGS → BASIC SETUP "Level",
LEVEL MODE "Height linearized"
Parameter name Description
➀
➁