Cerabar S/Deltabar S Description of parameters (FF configuration program)
Endress+Hauser 55
COUNTER_TMIN/
COUNTER: T < Tmin
Display
Index: 29
Data type: Unsigned16
Access: Read only
Displays the number of times the specified temperature range of the sensor has been
undershot. You can reset this counter by means of the RESET_TRANSMITTER_
OBSERVATION/ RESET PEAKHOLD parameter.
TEMPERATURE_1_MAX
_RESETABLE/
MIN. MEAS.TEMP.
Display
Index: 30
Data type: Float
Access: Read only
Displays the smallest measured temperature in the sensor (peak hold indicator). You can reset
this maximum indicator by means of the RESET_TRANSMITTER_OBSERVATION/RESET
PEAKHOLD parameter.
ELECTRONIC_OVER_
TEMPERATURE_
COUNTER/
PCB COUNT: T > Tmax
Display
Index: 31
Data type: Unsigned16
Access: Read only
Displays the number of times the specified temperature range of the electronics has been
overshot.
ELECTRONIC_OVER_
TEMPERATURE/
PCB MAX. TEMP.
Display
Index: 32
Data type: Float
Access: Read only
Displays the largest electronics temperature measured.
ELECTRONIC_UNDER_
TEMPERATURE_
COUNTER/
PCB COUNT: T <Tmin
Display
Index: 33
Data type: Unsigned16
Access: Read only
Displays the number of times the specified temperature range of the electronics has been
undershot.
ELECTRONIC_UNDER_
TEMPERATURE/PCB
MIN. TEMP.
Display
Index: 34
Data type: Float
Access: Read only
Displays the smallest electronics temperature measured.
Service Transducer Block
Parameter Description