Description of parameters (FF configuration program) Cerabar S/Deltabar S
56 Endress+Hauser
RESET_TRANSMITTER_
OBSERVATION/
RESET PEAKHOLD
Selection
Index: 35
Data type: Unsigned8
Access: Auto, OOS
This parameter lists all the peak hold indicator parameters that can be reset. You can select
the peak hold indicators you want to reset.
Options:
•None
• Max. meas. press.
• Min. meas. press.
•Pmax history
• Pmin history
•Max. temp.
•Min. temp.
•Tmax history
• Tmin history
•Reset all
Factory setting:
None
PRESSURE_1_AFTER_
DAMPING/
PRESSURE
Display
Index: 36
Data type: DS-65
Access: Read only
The PRESSURE_1_ AFTER_DAMPING parameter is a structured parameter consisting of two
elements.
VALUE
• Displays the measured pressure after sensor recalibration, position adjustment and
damping. This value corresponds to the PRIMARY_VALUE parameter in the "Pressure"
measuring mode.
STATUS
• Displays the status.
P01-xMD7xxxx-05-xx-xx-xx-011
!
Note!
You can transfer the value and status of the PRESSURE_1_AFTER_DAMPING parameter via
the CHANNEL parameter (→ Page 67) in the Analog Input Block. For this purpose, the
CHANNEL must be set to "3".
PRESSURE_1_AFTER_
CALIBRATION/
CORRECTED PRESS.
Display
Index: 37
Data type: Float
Access: Read only
Displays the measured pressure after sensor trim and position adjustment and before
damping.
→ See also the graphic, PRESSURE_1_AFTER_DAMPING/PRESSURE
TENDENCY/MEAS.
VAL. TREND
Display
Index: 38
Data type: Unsigned8
Access: Read only
Displays the trend of the pressure measured value.
Possibilities: increasing, decreasing, constant
MAX_TURNDOWN
Display
Index: 39
Data type: Float
Access: Read only
Displays the maximum possible turndown of the transmitter.
Service Transducer Block
Parameter Description
P
PV
Sensor
Analog
Input
Block
Pressure
Level
Flow
Damping
Position
adjust-
ment
Sensor
trim
Transducer Block
PRESSURE_1_
AFTER_DAMPING/
PRESSURE
PRESSURE_1_
AFTER_CALIBRATION/
CORRECTED PRESS.
PRESSURE_1_
AFTER_SENSOR/
SENSOR PRESSURE