Description of parameters (FF configuration program) Cerabar S/Deltabar S
60 Endress+Hauser
6.3.5 Display Transducer Block
Display Transducer Block
Parameter Description
DISPLAY_MAINLINE_
CONTENT/
MENU DESCRIPTOR
Selection
Index: 11
Data type: Unsigned8
Access: Auto, OOS
Specify contents for the main line of the on-site display in the measuring mode.
Options:
• Primary value (PV)
• Primary value (%)
• Pressure
•Flow
• Level
• Tank content
• Temperature
• Error number
• Totalizer 1
• Totalizer 2
The selection depends on the measuring mode chosen.
Factory setting:
Primary value (PV)
AUTOMATIC_
MAINLINE_FORMAT/
MAIN DATA FORMAT
Selection
Index: 12
Data type: Unsigned8
Access: Auto, OOS
Specifies the number of places after the decimal point for the value displayed in the main line.
Options:
•Auto
•x.x
•x.xx
•x.xxx
• x.xxxx
• x.xxxxx
Factory setting:
Auto
DISPLAY_
ALTERNATING_VALUES
/ALTERNATE DATA
Selection
Index: 13
Data type: Unsigned8
Access: Auto, OOS
Switch on "Alternating display" mode.
In this display mode, the on-site display alternates between the following measured values
depending on the measuring mode selected.
– Pressure: primary value (PV), primary value (%), pressure and temperature
– Level: primary value (PV), primary value (%), pressure, level, tank content and
temperature
– Flow: primary value (PV), primary value (%), pressure, flow, temperature, totalizer 1 and
totalizer 2
Options:
•Off
•On
Factory setting:
Off
DISPLAY_CONTRAST
Entry
Index: 15
Data type: Unsigned8
Access: Auto, OOS
Adjust contrast of on-site display.
You specify the contrast of the display with a number.
Input range:
4...13, 4: contrast weaker (brighter), 13: contrast stronger (darker).
Factory setting:
8
DISPLAY_LANGUAGE
Selection
Index: 16
Data type: Unsigned8
Access: Auto, OOS
Select the menu language for the on-site display.
Options:
•Deutsch
• English
• Français
• Italiano
•Español
• Nederlands
Factory setting:
English