Gammapilot M FMG60 with FOUNDATION Fieldbus Operation
Endress+Hauser 41
5.6.3 Network configuration
Prior to configuring the FF network, the device description (DD) of the Gammapilot M must be
downloaded to the directory provided.
Start the interface configuration tool.
Configure the interface.
Call the DD download routine.
Download the device descriptions (.ffo and .sym files) to the directory offered.
When the configuration is complete, close the tool and the FF stack (if open).
The Gammapilot M device descriptions can be ordered directly from Endress+Hauser or
downloaded from our website "www.endress.com". They contain all data necessary to operate
Endress+Hauser Foundation Fieldbus devices.
Example: Startup using the NI-Fieldbus configurator
Start the bus configuration tool. After startup, the tool shows the network configuration in the form
of an expandable tree. If the Gammapilot M has been connected correctly, it is now recognized:
A double click on the name reveals the device data:
The device ID is made up of the following components:
whereby:
A right-hand mouse click on the name opens up a menu from which the PD_TAG and
NODE_ADDRESS can be changed
E+H_GAMMAPILOT_M_XXXXXXXXXXX
PD_TAG the physical name of the device
DEVICE_ID the unique device identifier
NODE_ADDRESS Device address (is automatically allocated by the Configurator; can be changed subsequently
by the user)
Device_ID = 452B481013-XXXXXXXXXXX
452B48 ID code for Endress+Hauser
1013 ID code for Gammapilot M
XXXXXXXXXXX Device serial number, as printed on the nameplate