Gammapilot M FMG60 with FOUNDATION Fieldbus Operation
Endress+Hauser 45
5.6.6 Transducer block
Operation
The Transducer block contains the parameters required to calibrate the device. These parameters
can also be read out and edited using the VU331 display module. The calibration of the device is
described in Chapter 6.
The Transducer block is opened by clicking the "transducer" line.
Parameter changes from the tool are made off-line while the device is operating. The changes are
downloaded by first setting MODE_BLK = OOS then pressing the WRITE CHANGES button. If you
want to check all the values saved in the device, click READ ALL. To return to operation, set the
MODE_BLK to AUTO
6)
.
Block administration parameters
Output values
Configuration parameters
The Transducer block also contains the configuration parameters which are used to commission and
calibrate the device. They are identical to the functions of the operating menu, except for the service
parameters which are not accessible on the bus. Thus, the calibration procedure via the display
module ("Commissioning" section) is equally valid for a calibration via a network configuration tool.
A complete description of all the configuration parameters can be found in Operating Instructions
BA287F, "Gammapilot M FMG60 - Description of Device Functions".
E+H_GAMMAPILOT_M_XXXXXXXX
RESOURCE_XXXXXX (RB2)
TRANSDUCER_XXXXXX (TBUL)
ANALOG_INPUT_1_XXXXXX (AI)
6) If MODE_BLK refuses to be changed to AUTO, an error is present. Control all parameters, perform the required changes and try again to change MODE_BLK
to AUTO.
Parameter Description
MODE_BLK See description in Resource block. The possible operating modes of the Transducer block
are:
AUTO: the block is operating as normal
OOS: the block is out of service.
TAG_DESC User description of the intended application of the block.
BLOCK_ERROR Shows the error status in conjunction with the block components.
Out-of-service: the block is in OOS mode
Parameter Description
PRIMARY_VALUE Main value (level, level limit, density or concentration).
SECONDARY_VALUE Pulse rate
THIRD_VALUE Medium temperature