Gammapilot M FMG60 with FOUNDATION Fieldbus Commissioning
Endress+Hauser 65
6.3.5 "Measurement mode" (*05)
This function is used to select the desired measuring mode.
!
Note!
The selection can be performed only once and the function is automatically locked after that. It can
only be unlocked again by a reset of the Gammapilot M ("Reset" (*A3) function).
L00-FMG60xxx-05-00-00-xx-008
Possible measuring modes of the Gammapilot M: a: level measurement (continuous); b: level limit detection; c: density
measurement (with temperature compensation if required); d: concentration measurement (density measurement
followed by linearization)
Options:
level
limit
density (also with temperature compensation)
concentration (density measurement followed by linearization)
meas. mode *05
Âlevel
limit
density
ENDRESS + HAUSER
E
+
(a)
(b)
(c)
(d)
D
C