Commissioning Gammapilot M FMG60 with FOUNDATION Fieldbus
66 Endress+Hauser
6.3.6 "Density unit" (*06)
This function is needed for density and concentration measurements only. It is used to select the
density unit.
Options:
•g/cm
3
•g/l
lb/gal; [1g/cm
3
= 8,345 lb/gal]
•lb/ft
3
; [1g/cm
3
= 62,428 lb/ft
3
]
1°Brix = [270 (1 - 1/x)]
°Baumé; [1°Baumé = 144.3 (1 - 1/x)]
°API; [1°API = 131.5 (1.076/x - 1)]
°Twaddell; [1°Twaddell = 200 (x-1)]
"x" refers to the density in g/cm
3
. The formula indicates how many degrees this density corresponds
to.
6.3.7 "Min. density" (*07)
This function is needed for density and concentration measurements only. It is used to specify the
lower limit of the density range.
6.3.8 "Max. density" (*08)
This function is needed for density and concentration measurements only. It is used to specify the
upper limit of the density range.
density unit *06
Âg/cm3
g/l
lb/gal
ENDRESS + HAUSER
E
+
min. density *07
0.9500 g/cm
3
ENDRESS + HAUSER
E
+
max. density *08
1.2500 g/cm
3
ENDRESS + HAUSER
E
+