EasyManua.ls Logo

Endress+Hauser Gammapilot M FMG60 - Page 74

Endress+Hauser Gammapilot M FMG60
118 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Commissioning Gammapilot M FMG60 with FOUNDATION Fieldbus
74 Endress+Hauser
6.4.3 Full and empty calibration or covered and free calibration
Excerpt from the operating menu
The following excerpt from the operating menu shows how the full and empty calibration (for level
measurements) or the covered and free calibration (for level limit detection) are entered. The
individual functions are explained in the sections below.
The functions are only accessible after the background calibration has been performed.
L00-FMG60xxx-05-00-00-en-014
Note: The "value full." (*14) and "value empty" (*17) functions only appear if the "level" option has been selected in the
"measurement method" (*05) function.
"Calibration point" (*13)
This function is used to select which calibration point ("full/covered" or "empty/free") will be
entered.
Options:
•full/covered
empty/free
*15
calibration
0:stop/edit
1:start
*11
avg. pulse
rate
*16
full calibr.
[c/s]
-1:not calibrated
*13
calibr. point
0: full/covered
1:empty/free
1
E
0
*15
calibration
0:stop/edit
1:start
*11
avg. pulse
rate
*
[c/s]
18
emptycalibr.
-1:not calibrated
1
E
0
*14
value full
[%]
target value at
calibr. point
*17
value empty
[%]
target value at
calibr. point
*19
next
point
0:no
1: yes
Group
selection
calibr. point *13
Âfull/covered
empty/free
ENDRESS + HAUSER
E
+

Table of Contents

Other manuals for Endress+Hauser Gammapilot M FMG60

Related product manuals