EasyManua.ls Logo

Endress+Hauser Liquiline CA80SI - Ensuring the Degree of Protection; Post-Connection Check

Endress+Hauser Liquiline CA80SI
162 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Liquiline System CA80SI Electrical connection
Endress+Hauser 37
7.4.2 Bus address
Setting the bus address
1. Open the housing.
2. Set the desired bus address via the DIP switches of module 485.
For PROFIBUS DP, valid bus addresses are anything between 1 and 126, and anything
between 1 and 247 for Modbus. If you configure an invalid address, software
addressing is automatically enabled via the local configuration or via the fieldbus.
1
2
4
8
16
32
64
128
on off
A0026776
 52 Valid PROFIBUS address 67
1
2
4
8
16
32
64
128
on off
A0026777
 53 Valid Modbus address 195
1
2
4
8
16
32
64
128
on off
A0026778
 54
Invalid address 255
1)
1)
Order configuration, software addressing is active, software address configured at the factory: PROFIBUS 126,
Modbus 247
7.5 Ensuring the degree of protection
Only the mechanical and electrical connections which are described in these instructions
and which are necessary for the required, designated use, may be carried out on the device
delivered.
Exercise care when carrying out the work.
Individual types of protection permitted for this product (integrity (IP), electrical safety,
EMC interference immunity, Ex protection) can no longer be guaranteed if, for example:
Covers are left off
Different power units to the ones supplied are used
Cable glands are not sufficiently tightened (must be tightened with 2 Nm for the
confirmed level of IP protection)
Unsuitable cable diameters are used for the cable glands
Modules are not fully secured
The display is not fully secured (risk of moisture entering due to inadequate sealing)
Loose or insufficiently tightened cables/cable ends
Conductive cable strands are left in the device
7.6 Post-connection check
L
WARNING
Connection errors
The safety of people and of the measuring point is under threat. The manufacturer does
not accept any responsibility for errors that result from failure to comply with the
instructions in this manual.
Put the device into operation only if you can answer yes to all the following questions.

Table of Contents