Proline Promass E 300 PROFINET Diagnostics and troubleshooting
Endress+Hauser 163
Diagnostic behavior
(configurable)
Measured value status (fixed assignment)
Device diagnosis
(fixed assignment)
Quality
Quality
Substatus
Coding
(hex)
Category
(NE107)
Logbook entry only
GOOD ok 0x80 to 0x8E
Off
Diagnostic information 302
Diagnostic behavior
(configurable)
Measured value status (fixed assignment)
Device diagnosis
(fixed assignment)
Quality
Quality
Substatus
Coding
(hex)
Category
(NE107)
Alarm BAD
Function check,
local override
0x24 C Function check
Warning GOOD Function check 0xBC to 0xBF
Diagnostic information 302 (device verification active) is output during internal or
external Heartbeat verification.
Signal status: Function check
Choice of diagnostic behavior: alarm or warning (factory setting)
When Heartbeat verification starts, data logging is interrupted, the last valid measured
value is output and the totalizers are stopped.
Diagnostic information pertaining to the configuration: diagnostic number 400 to 599
Diagnostic behavior
(configurable)
Measured value status (fixed assignment)
Device diagnosis
(fixed assignment)
Quality
Quality
Substatus
Coding
(hex)
Category
(NE107)
Alarm BAD
Process
related
0x28
F
(Failure)
Invalid process
condition
Warning
UNCERTA
IN
Process
related
0x78
S
(Out of
specification)
Invalid process
condition
Logbook entry only
GOOD ok 0x80
Off
Diagnostic information pertaining to the process: diagnostic number 800 to 999
Diagnostic behavior
(configurable)
Measured value status (fixed assignment)
Device diagnosis
(fixed assignment)
Quality
Quality
Substatus
Coding
(hex)
Category
(NE107)
Alarm BAD
Process
related
0x28
F
(Failure)
Invalid process
condition
Warning
UNCERTA
IN
Process
related
0x78
S
(Out of
specification)
Invalid process
condition
Logbook entry only
GOOD ok 0x80
Off

Table of Contents