Commissioning Proline Promass E 300 PROFINET
118 Endress+Hauser
10.5.12 Configuring the low flow cut off
The Low flow cut off wizard systematically guides the user through all the parameters
that must be set to configure low flow cut off.
Navigation
"Setup" menu → Low flow cut off
Low flow cut off
Assign process variable
→  118
On value low flow cutoff
→  118
Off value low flow cutoff
→  118
Pressure shock suppression
→  118
Parameter overview with brief description
Parameter Prerequisite Description Selection / User
entry
Factory setting
Assign process variable Select process variable for low
flow cut off.
Off
Mass flow
Volume flow
Corrected volume
flow
*
On value low flow cutoff A process variable is selected
in the Assign process variable
parameter (→  118).
Enter on value for low flow cut
off.
Positive floating-
point number
Depends on country
and nominal
diameter
Off value low flow cutoff A process variable is selected
in the Assign process variable
parameter (→  118).
Enter off value for low flow cut
off.
0 to 100.0 %
Pressure shock suppression A process variable is selected
in the Assign process variable
parameter (→  118).
Enter time frame for signal
suppression (= active pressure
shock suppression).
0 to 100 s
* Visibility depends on order options or device settings