EasyManua.ls Logo

Endress+Hauser Proline Promass E 300 - Hardware Settings

Endress+Hauser Proline Promass E 300
264 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Electrical connection Proline Promass E 300 PROFINET
44 Endress+Hauser
Current input
31
4
2
A0028915
 17 Connection example for 4 to 20 mA current input
1 Power supply
2 Terminal box
3 External measuring device (to read in pressure or temperature, for instance)
4 Transmitter
Status input
1
2
3
A0028764
 18 Connection example for status input
1 Automation system with status output (e.g. PLC)
2 Power supply
3 Transmitter
7.5 Hardware settings
7.5.1 Setting the device name
A measuring point can be quickly identified within a plant on the basis of the tag name.
The tag name is equivalent to the device name (name of station of the PROFINET
specification). The factory-assigned device name can be changed using the DIP switches or
the automation system.
Example of device name (factory setting): EH-Promass300-XXXX
EH Endress+Hauser
Promass Instrument family
300 Transmitter
XXXX Serial number of the device
The device name currently used is displayed in Setup → Name of station is also displayed.

Table of Contents

Related product manuals