Proline Promass E 300 PROFINET Commissioning
Endress+Hauser 119
10.5.13 Configuring the partial filled pipe detection
The Partial filled pipe detection wizard guides you systematically through all parameters
that have to be set for configuring the monitoring of the pipe filling.
Navigation
"Setup" menu → Partially filled pipe detection
Partially filled pipe detection
Assign process variable
→  119
Low value partial filled pipe detection
→  119
High value partial filled pipe detection
→  119
Response time part. filled pipe detect.
→  119
Parameter overview with brief description
Parameter Prerequisite Description Selection / User entry
Assign process variable Select process variable for partially
filled pipe detection.
Off
Density
Reference density
Low value partial filled pipe
detection
A process variable is selected in the
Assign process variable parameter
(→  119).
Enter lower limit value for deactivating
partialy filled pipe detection.
Signed floating-point
number
High value partial filled pipe
detection
A process variable is selected in the
Assign process variable parameter
(→  119).
Enter upper limit value for deactivating
partialy filled pipe detection.
Signed floating-point
number
Response time part. filled pipe
detect.
A process variable is selected in the
Assign process variable parameter
(→  119).
Enter time before diagnostic message is
displayed for partially filled pipe
detection.
0 to 100 s