Diagnostics and troubleshooting Proline Promass E 300 PROFINET
180 Endress+Hauser
Diagnostic information Remedy instructions
No. Short text
302 Device verification active Device verification active, please wait.
Measured variable status
Quality Good
Quality substatus Function check
Coding (hex) 0xBC to 0xBF
Status signal C
Diagnostic behavior Warning
Influenced measured variables
• Oscillation amplitude 1
• Oscillation amplitude 2
• Application specific output
• Application specific output
• Signal asymmetry
• Carrier mass flow
• Carrier pipe temperature
• Target corrected volume flow
• Carrier corrected volume flow
• Concentration
• Measured values 1
• Measured values 2
• Measured values 3
• Oscillation damping 1
• Oscillation damping 2
• Density
• Oil density
• Water density
• Dynamic viscosity
• Sensor electronic temperature (ISEM)
• GSV flow
• GSV flow alternative
• Kinematic viscosity
• Mass flow
• Oil mass flow
• Water mass flow
• Index inhomogeneous medium
• Index suspended bubbles
• HBSI
• NSV flow
• NSV flow alternative
• External pressure
• Exciter current 1
• Exciter current 2
• Oscillation frequency 1
• Oscillation frequency 2
• S&W volume flow
• Reference density
• Reference density alternative
• Corrected volume flow
• Oil corrected volume flow
• Water corrected volume flow
• Oscillation damping fluctuation 1
• Oscillation damping fluctuation 2
• Frequency fluctuation 1
• Frequency fluctuation 2
• Target mass flow
• Carrier volume flow
• Target volume flow
• Temp. compensated dynamic viscosity
• Temp. compensated kinematic viscosity
• Temperature
• Status
• Volume flow
• Oil volume flow
• Water volume flow
• Water cut
Diagnostic information Remedy instructions
No. Short text
303 I/O 1 to n configuration changed 1. Apply I/O module configuration (parameter 'Apply I/O configuration')
2. Afterwards reload device description and check wiring
Measured variable status
Quality Good
Quality substatus Ok
Coding (hex) 0x80 to 0x83
Status signal M
Diagnostic behavior Warning
Influenced measured variables
–