Proline Prowirl 73 Description of device functions
Endress+Hauser 155
REFERENCE GROSS
CALORIFIC VALUE
Prerequisite
The function is only available if NATURAL GAS AGA8 Gross Method 1 or NATURAL
GAS SGERG-88 was selected in the NATURAL GAS EQUATION function (ä 149).
Description
Use this function to enter the reference gross calorific value of the natural gas. The
following reference operating conditions apply: reference temperature 0°C, reference
pressure 1.013 bar abs, reference combustion temperature 25°C. The reference gross
calorific value is used for the calculation of the compressibility of the natural gas with the
natural gas equations AGA8 Gross Method 1 and SGERG-88.
User input
5-digit floating-point number
Unit
The corresponding unit is taken from the UNIT CALORIFIC VALUE CORRECTED
VOLUME function.
Factory setting
34 MJ/Nm
3
TYPE CALORIFIC
VALUE
Prerequisite
The function is only available if the following was selected in the SELECT FLUID
function (ä 143):
• NATURAL GAS
•METHANE
• USER DEFINED LIQUID
• GAS MIXTURE
Description
Use this function to define the type of unit for the net calorific values and gross calorific
values:
• "per mass", e.g. MJ/kg
• "per corrected volume", e.g. kBtu/SCF
Options
MASS
CORRECTED VOLUME
Factory setting
CORRECTED VOLUME
GROSS CALORIFIC
VALUE
Prerequisite
The function is only available if the following was selected in the SELECT FLUID
function:
•METHANE
• USER DEFINED LIQUID with COMBUSTION option in the
ENERGY CALCULATION function
• GAS MIXTURE
or if the selection NATURAL GAS and one of the following NATURAL GAS EQUATION
was selected in the SELECT FLUID section:
• AGA8-DC92
• ISO 12213-2
• AGA8 Gross Method 1
•SGERG 88
Description
• A gross calorific value, which is used to calculate the heat flow, can be entered here
for USER DEFINED LIQUIDS.
• The gross calorific value of the gas is displayed here in the other cases described. The
gross calorific value is calculated as per ISO 6976-1995.
!
Note!
Make sure that the correct reference combustion temperature was entered (ä 153)
User input/user interface
5-digit floating-point number
Factory setting
40MJ/kg ; the corresponding unit is taken from the UNIT CALORIFIC VALUE MASS or
UNIT CALORIFIC VALUE CORRECTED VOLUME function.
Function description, FLOW COMPUTER group