Description of device parameters Waterpilot FMX21
94 Endress+Hauser
Description Enter the number of the current point in the table. Subsequent entries in "X-val" and "Y-val"
relate to this point.
Input range 1...32
X-val
Write permission Operators/Service engineers/Expert
Description Enter the X-value (level before linearization) for the specific point in the table and confirm.
Note • If "Lin. mode" = "Manual", the level value must be entered.
• If "Lin. mode" = "Semiautomatic", the level value is displayed and must be confirmed by
entering the paired Y-value.
Y-value
Ceramic
Write permission Operators/Service engineers/Expert
Description Enter the Y-value (value after linearization) for the specific point in the table. The unit is
determined by "Unit after lin.".
Note The linearization table must be monotonic (increasing or decreasing).
Edit table
Write permission Operators/Service engineers/Expert
Description Select the function for entering the table.
Options • Next point: Enter the next point.
• Current point: Stay on the current point to correct a mistake, for example.
• Last point: Skip back to the previous point to correct a mistake, for example.
• Insert point: Insert an additional point (see example below).
• Delete point: Delete the current point (see example below).